AC Not Cooling: Grounded Compressor Case

When your AC is blowing air but not cooling, the issue might be deeper than you think. Here’s how a grounded compressor led to a full system replacement.

 

🏠 Customer Complaint: “The AC is running, but the room isn’t cooling”

A few days ago, I received a service call from a homeowner who said, “Cool air is coming out, but the room still feels hot.” On arrival, I confirmed that the indoor unit was blowing air just fine, but the temperature in the house wasn’t dropping at all.

 

This kind of issue is more common than you might think during the summer months. While it may seem like a simple thermostat problem at first glance, there are actually several possible causes that can lead to this symptom. From incorrect thermostat settings to major component failures—like a compressor burnout—diagnosing the real issue requires a step-by-step inspection.

 

When an air conditioner is blowing air but not cooling the space, it means the airflow system is working, but the cooling cycle isn’t. That’s a critical clue. It tells us that the fan motor is operating, but the refrigerant circuit might not be. It could be something as simple as a tripped breaker or as serious as a grounded compressor.

 

In this case, I approached the problem by first checking the thermostat settings and ensuring the system was in cooling mode. Once I confirmed that, I moved on to inspect the outdoor unit to see whether the compressor and condenser fan were actually running. What I found revealed a deeper electrical issue that required further testing.

 

This kind of service call is a reminder that just because something seems to be working doesn’t mean the system as a whole is functioning properly. The air might be moving, but without the cooling function, it’s like a car engine running without the wheels turning.

 

In the rest of this post, I’ll walk you through exactly how I diagnosed the issue, what tools I used, and how I determined that the compressor had an electrical ground fault that ultimately required a full system replacement. Whether you're a homeowner or a new HVAC tech, this breakdown might help you understand what’s really going on when your AC isn’t doing its job.

 

🧰 Step 1: Thermostat Settings and Outdoor Unit Inspection

Upon arriving at the customer's home, my first step was to check the thermostat settings. I switched the system to Cooling Mode and adjusted the temperature to ensure it would trigger the air conditioning cycle. The indoor fan started running normally, and air was flowing through the vents—but it wasn’t cold at all.

 

This is a critical observation. If the fan is blowing but the air feels warm, it usually indicates that the blower system is functional, but the refrigerant cycle isn’t active. In most cases, this means something is wrong with the outdoor unit, which is responsible for releasing heat absorbed from inside the home.

 

I proceeded to the outdoor condensing unit and turned the system back on to observe what would happen. I heard the familiar “click” sound coming from the contactor, which meant the thermostat was successfully sending a signal to the outdoor unit. However, neither the compressor nor the condenser fan started running.

 

That click without any motor movement is a red flag. It usually points to one of three things: a power supply issue, a failed capacitor, or a serious internal failure like a grounded compressor.

 

At this stage, I knew the system was receiving the thermostat signal, but something inside the outdoor unit was preventing the compressor and fan from starting. The entire outdoor unit appeared to be completely non-operational, despite the initial signal being received. This meant I had to dig deeper—starting with electrical checks to confirm whether voltage was actually reaching the unit.

 

This first inspection step is often overlooked, but it sets the foundation for accurate diagnosis. Without it, you might assume the system just needs refrigerant or that the thermostat is malfunctioning. In reality, the source of the problem could be hidden within the unit’s electrical components—and that’s exactly where I was headed next.

 

⚡ Step 2: Electrical Troubleshooting — Finding the Power Problem

Once I confirmed that the outdoor unit wasn’t responding, my next step was to open up the unit’s electrical panel and perform a voltage check using a multimeter. I set the meter to AC voltage mode and tested the terminals at the bottom of the contactor—this is where power should be entering the unit.

 

To my surprise, the reading showed 0 volts. This meant that the contactor wasn’t receiving any power at all. Even though the thermostat had signaled the unit to start, electricity wasn’t making it to the critical components like the compressor or condenser fan. This wasn’t just a faulty part—it looked like a total power loss.

 

I traced the electrical wiring back to the disconnect box, which was mounted next to the outdoor unit. These boxes typically serve as a safety shutoff and are often the site of blown fuses or loose connections. I carefully opened the disconnect cover and measured voltage across the terminals inside. Still no power—another 0V reading.

 

At this point, I knew the issue had to be upstream—likely at the main electrical panel inside the home. Sure enough, when I inspected the panel, I found that the 60-amp circuit breaker dedicated to the outdoor unit had tripped.

 

Now, it might seem like a simple fix to just reset the breaker and turn the unit back on—but that can be dangerous. Circuit breakers don’t trip for no reason. They’re designed to cut power in response to a serious problem, such as a short circuit, overload, or grounded component. Resetting it blindly without investigating the root cause can risk further damage—or even an electrical fire.

 

This is where many homeowners or even inexperienced technicians can go wrong. Simply flipping the breaker may restore temporary power, but it doesn’t solve the underlying issue. In fact, it could make things worse if the equipment is compromised.

 

Instead of rushing to reset the breaker, I paused and prepared to conduct an insulation resistance test on the compressor using a megohmmeter. This would allow me to verify whether the compressor had shorted to ground—a serious fault that could be responsible for tripping the breaker in the first place.

 

🔍 Step 3: Verifying Compressor Insulation with a Megohmmeter

Before attempting to reset the tripped breaker and reapply power to the outdoor unit, I needed to investigate a possible ground fault in the compressor. One of the most common reasons a breaker trips and cuts power to an air conditioning system is a grounded compressor—a dangerous and often costly problem.

 

To check this, I used a megohmmeter (also known as a “megger”) to perform an insulation resistance test. This tool sends a high-voltage, low-current signal through the motor windings to detect whether electricity is leaking to ground—something a standard multimeter won’t reveal.

 

Before testing, I disconnected all three wires connected to the compressor from the contactor. This step is essential to ensure accurate readings and avoid interference from other components. I highly recommend that anyone doing this take a clear photo of the wire connections before disconnecting them, to make sure they can be reconnected correctly later. One small wiring mistake can lead to further system failures.

 

With the wires safely removed, I touched one lead of the megohmmeter to a single compressor terminal and the other lead to the metal case of the condenser, which serves as ground. Then, I pressed the test button.

 

The result: “BAD”—meaning the compressor’s winding was leaking current directly to ground. I repeated the test on the other two terminals just to confirm, and each time, the megohmmeter indicated a failure in insulation.

 

This is a clear indicator that the compressor is electrically grounded internally, likely due to a winding short or internal burn-out. At this point, it was no longer a question of repair—it was a confirmation that the compressor had failed completely and was not safe to power back on.

 

⚠️ Pro Tip: Always photograph wiring before disconnecting anything. It might save you hours of troubleshooting later.

 

Finding a grounded compressor is never good news, but it’s far better to discover it through proper testing than to restore power and risk a blown breaker or worse. This test not only pinpointed the exact issue but also validated that replacing the compressor—or more likely, the entire outdoor unit—was necessary.

 

🔥 Step 4: Visual Inspection – Burn Marks and Odor Reveal Internal Damage

After confirming with the megohmmeter that the compressor was likely grounded, I decided to conduct a visual inspection to further validate the diagnosis. Electrical faults often leave physical evidence, and in HVAC systems, visual signs like scorching or burned terminals can offer clear insight into internal damage.

 

To do this, I first removed the top cover of the outdoor unit, which includes the condenser fan assembly. This gave me direct access to the compressor housing. As soon as I opened it, I was met with a familiar but unpleasant sign—a faint burning smell that typically signals electrical failure.

 

Upon closer examination of the compressor terminals, I noticed significant burn marks on one of the connection points. The insulation surrounding the terminal wire looked charred and partially melted, and the terminal itself was darkened from heat exposure. This kind of thermal damage often occurs when internal windings short out and begin arcing against the casing or terminal lugs.

 

Even though I had already run a megohmmeter test, I decided to perform one more insulation resistance test just to be sure. Once again, the result was “BAD”, confirming that the compressor’s internal windings were still leaking current to ground. Combined with the visible signs of electrical damage and the persistent burnt odor, it was now 100% clear that the compressor had completely failed.

 

What’s important here is the combination of test results and physical evidence. A megger reading alone might indicate a problem, but pairing that with visible charring and the scent of burnt wiring removes all doubt. The compressor wasn’t just struggling—it was beyond repair.

 

This kind of failure typically stems from years of wear, overheating, improper voltage, or even moisture inside the system. In this case, the damage was severe enough that replacing just the compressor wouldn’t be a wise investment. The better option would be to plan for complete outdoor unit replacement, especially since the system used outdated R-22 refrigerant.

 

For technicians, this step reinforces the value of using both instruments and intuition. The smell, the visuals, and the test results all told the same story: this system was done. And that’s a decision no one wants to make—but one that needs to be based on evidence, not guesswork.

 

♻️ Step 5: Replacement Plan – Upgrading to a Modern Refrigerant System

After confirming that the compressor was electrically grounded and physically damaged, it was time to talk solutions. In this case, simply replacing the compressor wasn’t the best option—the system was running on outdated R-22 refrigerant, which is no longer manufactured or supported in many regions due to environmental regulations.

 

R-22 systems are becoming increasingly expensive to maintain, and sourcing compatible parts or refrigerant is getting harder every year. Even if a new compressor could be installed, the long-term reliability and cost-efficiency would still be questionable. For these reasons, replacing the entire outdoor condensing unit was the most practical and future-proof decision.

 

Fortunately, the indoor evaporator coil was a newer model already rated for R-410A, which made the upgrade process slightly easier. However, the system I planned to install used an even more modern refrigerant—R-454B, a next-generation A2L refrigerant designed to meet updated environmental standards while improving energy efficiency.

 

R-454B is mildly flammable (A2L classification), which means certain safety features and compatible components must be installed along with it. These aren't optional—they’re required by code in many jurisdictions and critical for safe operation.

 

Here are the key upgrades needed for an R-454B retrofit:

  • 🧪 Leak Detection Device: R-454B requires a continuous refrigerant leak detector, especially in enclosed spaces, to alert users in case of leaks.
  • 💡 A2L-Compatible Control Board: Standard control boards are not designed for A2L refrigerants and must be replaced with models specifically rated for use with these substances. These boards are built to safely shut down the system in the event of a leak or fault.
  • 🌀 Evaporator Coil Upgrade (if needed): In this case, even though the existing coil was compatible with R-410A, it still required replacement because R-454B systems often come as matched units to meet strict performance and safety standards.

These upgrades not only allow the system to function efficiently with the new refrigerant, but they also ensure compliance with safety codes and manufacturer warranties. Cutting corners here could lead to performance issues or even code violations later on.

 

By investing in a complete system upgrade now, the homeowner avoids future compatibility issues, benefits from lower energy bills, and enjoys a more environmentally friendly system built to last.

 

✅ Conclusion

In this case, a seemingly minor issue—“cool air not cooling the room”—turned out to be a serious electrical fault inside the compressor. Through step-by-step testing, visual inspection, and careful analysis, we uncovered the real cause: a grounded compressor that rendered the entire system inoperable. Instead of a quick fix, the solution was a full upgrade to a modern R-454B refrigerant system.

 

For HVAC technicians, this story highlights the importance of thorough diagnostics. And for homeowners, it’s a reminder that professional evaluation can prevent bigger issues down the line. Whether you're troubleshooting your own unit or learning from the field, knowing what to look for—and when to upgrade—makes all the difference.

 